What should be taken into account when connecting to the drainage system?
- The materials used for the inlet and outlet pipes must be resistant to oily waste water.
- The required pipe cross-sections (depending on the nominal size of the separator) and the required pipe gradient (min. 2%) in accordance with the relevant standards must be observed.

2 Excess depth/raised edge
3 Drainage surface
Head in accordance with DIN EN 858-2
Separator systems must be installed in such a way that the upper edge of the cover is positioned sufficiently high above the relevant level of the area to be drained.
This prevents the light liquids from escaping from the system!