Skip to main content

Retrofit kit Aqualift S

Duo, GTF 1200-S3

PDF product data sheet

The retrofit kit for installation in existing collection tanks for faecal-free wastewater is equipped with two submersible pumps, a backflow preventer and a manual locking device. The polymer profile (PE) is used to mount and fix the pumping station. Quick-release closures enable easy removal of the pumps. The station is controlled either by a float switch or by a user-friendly control unit, which can be optionally integrated in the building control system via a voltage-free contact. Alternatively, alarm and collective fault messages can be output via a GSM interface.

Item no. AQUALI1200DS
Discount group 3

Retrofit kit Aqualift S Duo, GTF 1200-S3
The retrofit kit for installation in existing collection tanks for faecal-free wastewater is equipped with two submersible pumps, a backflow preventer and a manual locking device. The polymer profile (PE) is used to mount and fix the pumping station. Quick-release closures enable easy removal of the pumps. The station is controlled either by a float switch or by a user-friendly control unit, which can be optionally integrated in the building control system via a voltage-free contact. Alternatively, alarm and collective fault messages can be output via a GSM interface. Version: Type of system: Twin pump station Pump control: Control unit Backflow preventer: integrated Delivery state: Modular set for assembly on site Installation situation: installation in on-site collecting tank Type of wastewater: wastewater without sewage General characteristics: Standard: EN 12050-2 Tank: Pressure pipe connection: horizontal Pressure pipe connection (DN): 32 mm Pressure pipe connection (OD): 40 mm Pumping device: Pump: GTF 1200 Number of pumps: 2 Max. pumping capacity: 15.5 m3/h Max. pumping height: 9 m Operating mode: S3 - 50 % Power P1: 1.4 kW Power P2: 0.84 kW Speed: 2,650 U/min Max. temperature (permanent) of conveyed material: 40 °C Connection type: coded plug Weight: 10 kg Impeller type: Multi-vane impeller Length of mains cable for pump: 10 m Rated current: 6.2 A Protection class (pump): IP 68 (3m) Protection class: I Type of pump connection cable: H07RN-F 3G 1.0 mm2 Temperature monitoring: integrated Cos phi - power factor: 0.98 Expected service life (number of switching cycles): 150,000 Expected service life (hours of operation): 5,000 Std Insulation class: F Max. permissible switching frequency: 20 1/h Control: Control unit: Comfort Operating voltage: 230 V Mains frequency: 50 Hz Self-diagnosis system (SDS): yes Battery buffering: yes Multi-line display: yes Log book function: yes USB interface: yes GSM interface: yes Potential-free contact: optional Type of fuse required (electrical protection): C 16 A Protection class control unit: IP 54 Length of mains cable for control unit: 1.4 m Level measurement instrument: Float switch
  Title Item no.  
  Title Item no.  
  Title Item no.  
  Title Item no.  
  • Start-up current (ATTR-285): 14.9  AMP
  • Pump (ATTR-4): GTF 1200
  • Number of pumps (ATTR-181): 2
  • Impeller type (ATTR-8): Multi-vane impeller
  • Type of pump connection cable (ATTR-N2): H07RN-F 3G 1.0 mm2
  • Max. permissible switching frequency (ATTR-162): 20  1PH
  • Operating mode (ATTR-10): S3 - 50 %
  • Power P1 (ATTR-F4): 1.4  KWT
  • Power P2 (ATTR-F5): 0.8  KWT
  • Speed (ATTR-F2): 2,650  UMIN
  • Rated current (ATTR-N5): 6.2  AMP
  • Max. pumping capacity (ATTR-F7): 15.5  MQH
  • Max. pumping height (ATTR-F8): 9  MTR
  • Max. temperature (permanent) of conveyed material (ATTR-132): 40  CEL
  • Protection class (ATTR-133): I
  • Connection type (ATTR-N1): coded plug
  • Protection class (pump) (ATTR-125): IP 68 (3m)
  • Length of mains cable for pump (ATTR-11): 10  MTR
  • Temperature monitoring (ATTR-135): integrated
  • Weight (ATTR-191): 10  KGM
  • Cos phi - power factor (ATTR-192): 1.0
  • Insulation class (ATTR-193): F
  • Expected service life (hours of operation) (ATTR-194): 5,000  HUR
  • Expected service life (number of switching cycles) (ATTR-195): 150,000
  • Net weight (ATTR-A3A): 0  KGM
  • Gross weight (ATTR-A3B): 0  KGM
  • Number of packages (ATTR-321): 0
  • Pressure pipe connection (ATTR-B7): horizontal
  • Type of system (ATTR-2): Twin pump station
  • Backflow preventer (ATTR-165): integrated
  • Pump control (ATTR-134): Control unit
  • Control unit (ATTR-S2): Comfort
  • Self-diagnosis system (SDS) (ATTR-S5): yes
  • Battery buffering (ATTR-S6): yes
  • Multi-line display (ATTR-S7): yes
  • Log book function (ATTR-S8): yes
  • USB interface (ATTR-S9): yes
  • GSM interface (ATTR-S10): yes
  • Potential-free contact (ATTR-S11): optional
  • Length of mains cable for control unit (ATTR-S12): 1.4  MTR
  • Operating voltage (ATTR-S13): 230  VLT
  • Mains frequency (ATTR-S14): 50  HTZ
  • Protection class control unit (ATTR-S4): IP 54
  • Level measurement instrument (ATTR-7B): Float switch
  • Type of fuse required (electrical protection) (ATTR-S17): C 16 A
  • Pressure pipe connection (DN) (ATTR-B17): 32  MMT
  • Pressure pipe connection (OD) (ATTR-B18): 40  MMT
  • Type of wastewater (ATTR-6): wastewater without sewage
  • Standard (ATTR-9): EN 12050-2
  • Installation situation (ATTR-1): installation in on-site collecting tank
  • Delivery state (ATTR-189): Modular set for assembly on site
  • Brand (M-ATTR-001): KESSEL
  • Product group (M-ATTR-002): Lifting stations
  • Product type (M-ATTR-003): Retrofit kit
  • Product family (M-ATTR-004): Aqualift
  • Product name (M-ATTR-005): Aqualift S